Honeywell HM750A1000
>>
Maintenance Schedule
>>
Replace Cylinder
Description
Instructions
Disconnect main power source before accessing internal compartments. 1. Drain the existing cylinder by pressing the Power/Drain button on the front of the humidifier for 1 second. Let the humidifier drain until no more water is flowing out to drain (usually not more than 10 minutes). Following the drain cycle, the humidifier will switch off. 2. Close the supply water shut off valve. 3. Turn off power to the humidifier with the external disconnect. 4. Using a flat screwdriver, turn the lock on the humidifier’s front cover 90° counterclockwise to release. Rotate the base of the cover outwards 6 inches, then lift upwards to remove. Fig. 28. Removing the cover. 5. Remove the high level water sensor connections. 6. Remove the cylinder plugs from the cylinder pins by pulling vertically. 7. Using a flat screwdriver or 5/16 in. nut driver, loosen the hose clamp closest to the cylinder. 8. Pull the cylinder away from the steam hose to disengage. When free of steam hose, lift the cylinder out. 9. Some water may remain in the cylinder, even after fully draining. Have a cloth available to absorb any water. Seat new cylinder into drain housing first and then connect steam hose. Reconnect 3 terminals.
Task Type
Preventive
Inspection
Clean
Repair
Modify
Takes asset out of service
Priority
Low
Medium
High
Estimate
Hours
Part
Quantity
Canister
1
ea.
Triggers
By Time
Every
Hours
Days
Months
Years
Starting At
Years
Limit
occurences
No public attachments